PERFORMANCE ASSESSMENT OF A NON-PERFORATED DOUBLE-PLATE DIFFUSER USING CFD UNDER VARIABLE FLOW RATES IN A STRATIFIED CHILLED-WATER STORAGE TANK

Authors

  • Pattana Mekkhum University of Phayao
  • Poramate Sittisun University of Phayao
  • Kaweewat Worasaen King Mongkut’s University of Technology North Bangkok
  • Nopparat Katkhaw University of Phayao

Keywords:

chilled-water thermal energy storage, thermal stratification, non-perforated double-plate diffuser, computational fluid dynamics, thermal energy storage performance

Abstract

A stratified chilled-water storage tank is an important cool thermal energy storage technology for reducing peak electricity demand in air-conditioning systems because it can shift chilled-water production from high-demand periods to off-peak periods. The performance of this type of tank depends strongly on the sharpness of the thermocline, which is mainly governed by the flow structure near the inlet–outlet region and the diffuser configuration. This study aims to evaluate the performance of a non-perforated double-plate diffuser under variable flow rates using a reference geometry with dp/D = 0.75 and hp/di ≈ 0.455, obtained from a preceding study. Transient two-dimensional computational fluid dynamics simulations were performed in ANSYS Fluent for the discharge process at flow rates of 1.5, 2.5, and 3.5 L/min, with an initial tank temperature of 5 °C and return-water temperature of 15 °C. The simulation results were analyzed to determine the thermocline thickness within the 0.40–0.77 m evaluation window, the dimensionless Re and Ri, and the energy-based performance indices, including ½FOM, lost capacity, and Equivalent Lost Height (ELH). The results showed that the flow rate of 3.5 L/min provided the best overall performance within the investigated range, with the minimum thermocline thickness of 0.1516 m, the highest ½FOM of 0.748, and the lowest lost capacity and ELH of 1.962 MJ and 0.093 m, respectively. In contrast, the flow rate of 2.5 L/min showed the least favorable performance in the present dataset. These results indicate that selecting an appropriate flow rate together with the diffuser geometry affects the reduction of mixing inside the tank, the preservation of a sharper thermocline, and the improvement of the energy performance of a stratified chilled-water storage tank.

References

Abd Majid, M. A., Muhammad, M., Hampo, C. C., & Akmar, A. B. (2020). Analysis of a thermal energy storage tank in a large district cooling system: A case study. Processes, 8(9), 1158. https://doi.org/ 10.3390/pr8091158

Alesbe, I., Abdul Wahhab, H. A., & Aljabair, S. (2023). Transient study of thermal stratification of full-scale chilled water storage tank during optimum discharge condition. Journal of Energy Storage, 65, 107236. https://doi.org/10.1016/j.est.2023.107236

Bahnfleth, W. P., & Musser, A. (1998). Thermal performance of a full-scale stratified chilled-water thermal storage tank. ASHRAE Transactions, 104(2), 377–388.

Bahnfleth, W. P., Song, J., & Cimbala, J. M. (2003). Measured and modeled charging of a stratified chilled water thermal storage tank with slotted pipe diffusers. HVAC&R Research, 9(4), 467–491. https://doi.org/10.1080/10789669.2003.10391075

Deng, Y., Sun, D., Niu, M., Yu, B., & Bian, R. (2021). Performance assessment of a novel diffuser for stratified thermal energy storage tanks—The nonequal-diameter radial diffuser. Journal of Energy Storage, 35, 102276. https://doi.org/10.1016/j.est.2021.102276

Glazer, J. (2019). ASHRAE design guide for cool thermal storage (2nd ed.). ASHRAE.

Jodeiri, A. M., Soppelsa, A., Turrin, F., Pipiciello, M., Cozzini, M., & Fedrizzi, R. (2024). Numerical and experimental investigation of stratified water storage tanks: An enhanced adaptive-grid model. Applied Thermal Engineering, 248, 123113. https://doi.org/10.1016/j.applthermaleng.2024.123113

Karim, M. A. (2011). Experimental investigation of a stratified chilled-water thermal storage system. Applied Thermal Engineering, 31(11–12), 1853–1860. https://doi.org/10.1016/j.applthermaleng.2010.12.019

Kereikulova, A., Yerdesh, Y., Belyayev, Y., Toleukhanov, A., Botella, O., Kheiri, A., & Khalij, M. (2026). Impact of inlet configuration and flow rates on thermal storage stratification and efficiency. Thermo, 6(1), 16. https://doi.org/10.3390/thermo6010016

Li, Q., Lin, W., Huang, X., Tai, Y., Ding, X., Zhang, Y., & Gao, W. (2022). Thermocline dynamics in a thermally stratified water tank under different operation modes. Applied Thermal Engineering, 212, 118560. https://doi.org/10.1016/j.applthermaleng.2022.118560

Lou, W., Baudin, N., Roux, S., Fan, Y., & Luo, L. (2023). Impact of buoyant jet entrainment on the thermocline behavior in a single-medium thermal energy storage tank. Journal of Energy Storage, 71, 108017. https://doi.org/10.1016/j.est.2023.108017

Moncho-Esteve, I. J., Gasque, M., González-Altozano, P., & Palau-Salvador, G. (2017). Simple inlet devices and their influence on thermal stratification in a hot water storage tank. Energy and Buildings, 150, 625–638. https://doi.org/10.1016/j.enbuild.2017.06.012

Parida, D. R., Advaith, S., Dani, N., & Basu, S. (2022). Assessing the impact of a novel hemispherical diffuser on a single-tank sensible thermal energy storage system. Renewable Energy, 183, 202–218. https://doi.org/10.1016/j.renene.2021.10.099

Tipasri, W., & Wongwuttanasatian, T. (2019). Effect of height to diameter ratio of chilled water storage tank on temperature gradient during discharging. Energy Procedia, 156, 254–258. https://doi.org/10. 1016/j.egypro.2018.11.138

Wang, X., Duan, L., Gao, G., Zheng, W., Sun, D., Li, J., Fu, J., & Lin, R. (2025). Analysis and optimization of thermal storage performance of thermocline storage tank with different water distribution structures. Processes, 13(3), 629. https://doi.org/10.3390/pr13030629

Weiss, J., Ortega-Fernández, I., Müller, R., Bielsa, D., & Fluri, T. (2021). Improved thermocline initialization through optimized inlet design for single-tank thermal energy storage systems. Journal of Energy Storage, 42, 103088. https://doi.org/10.1016/j.est.2021.103088

Xing, Y., Zhang, X., Zhang, Z., & Liu, F. (2024). The impact of inlet structure on stratification performance in thermal storage tanks: A study through simulation and experimental analysis. Applied Sciences, 14(12), 5248. https://doi.org/10.3390/app14125248

Xu, C., Liu, M., Jiao, S., Tang, H., & Yan, J. (2022). Experimental study and analytical modeling on the thermocline hot water storage tank with radial plate-type diffuser. International Journal of Heat and Mass Transfer, 186, 122478. https://doi.org/10.1016/j.ijheatmasstransfer.2021.122478

Yaïci, W., Ghorab, M., Entchev, E., & Hayden, S. (2013). Three-dimensional unsteady CFD simulations of a thermal storage tank performance for optimum design. Applied Thermal Engineering, 60(1–2), 152–163. https://doi.org/10.1016/j.applthermaleng.2013.07.001

Downloads

Published

2026-11-24

How to Cite

Mekkhum, P., Sittisun, P., Worasaen, K., & Katkhaw, N. (2026). PERFORMANCE ASSESSMENT OF A NON-PERFORATED DOUBLE-PLATE DIFFUSER USING CFD UNDER VARIABLE FLOW RATES IN A STRATIFIED CHILLED-WATER STORAGE TANK. Journal of Science and Technology Thonburi University, 10(2), 32–52. Retrieved from https://ph03.tci-thaijo.org/index.php/trusci/article/view/4818